Define the Interface and Control Objective
Choose a sludge blanket sensor by matching the measurement principle to the tank, sludge, and control strategy. Ultrasonic systems provide continuous, real-time interface-level monitoring, while optical probes detect the liquid-solids interface by automatically adjusting light intensity for changing sludge concentrations. Tank geometry, sludge properties, fouling, installation access, setpoint logic, and required outputs determine the fit. Collect those site inputs before comparing proposals against measurement range, controls, communications, maintenance, and acceptance criteria.
Define whether the instrument is for local display, alarms, underflow-pump control, analog control, centralized monitoring, or a combination. A sludge blanket depth reading measures the accumulated blanket thickness; the location of that blanket measured downward from the liquid surface is a different configuration. Markland offers a detector that can read sludge depth upward from the tank bottom or blanket location downward from the liquid surface, so specify the required datum rather than accepting a generic “level” output.
Request the tank process description, intended sludge inventory limits, existing pump-control logic, and the operational consequences of an incorrect or missing reading. That record should identify whether a high blanket threatens carryover, whether drawing sludge too frequently reduces solids recovery, and how the underflow pumps, alarms, and PLC currently interact. If loss of the measurement could cause an unsafe pump condition, the failure state belongs in the control specification rather than being left to the supplier’s default configuration.
Match Sensor Technology to Tank Conditions
Select the measurement principle only after reviewing the tank geometry and expected sludge behavior. Badger Meter describes EchoSmart as an underwater, digital-platform ultrasonic interface-level analyzer for continuous, real-time measurement. Markland describes a submerged vertical optical probe using infrared light, with automatic beam-intensity adjustment for different sludge concentrations. These architectures should be evaluated against the same tank conditions, including mounting access, expected solids variation, obstructions, and fouling.
| Discharge route or influent problem | Governing rule or process option | What data settles it |
|---|---|---|
| Clarifier or DAF with surface skimmers | Badger Meter identifies a standard EchoSmart sensor with multi-flex assembly for installations where surface skimmers are present. | A dimensioned drawing showing skimmer position, sweep path, probe location, and required clearance. |
| Tank without surface skimmers | Badger Meter identifies a self-cleaning EchoSmart sensor for applications without surface skimmers. | Whether the sensor can rotate freely and whether the self-cleaning mechanism suits the available maintenance access. |
| Water-clarity information is required in addition to blanket position | Badger Meter offers a sensor with turbidity to provide further insight into water clarity. | The control objective, output requirements, and a clear definition of how turbidity will be used by operators. |
| Constricted or obstructed installation with a vertical optical probe | Markland describes a slim, submerged optical probe that can be used in obstructed or constricted areas. | Mounting dimensions, obstruction locations, cable route, extraction space, and representative sludge behavior. |
| Blanket range must extend across the tank depth | The cited Markland configuration is adjustable from 0–700 cm or in. | Minimum and maximum expected interface positions measured from the supplier-defined datum. |
Request the proposed probe arrangement and measurement resolution for optical selection. Markland states that its probe uses 64 pairs of infrared LED/phototransistor elements spaced vertically at 19 mm (¾ in.) centers, with an adjustable range of 0–700 cm or in. That arrangement supports comparison, but it does not remove the need to establish the operating range, interface location, and required accuracy for the actual tank.
Treat sludge concentration, settling rate, grease, fibers, abrasive solids, and turbulence as unresolved site inputs because the available product descriptions do not establish a universal sensor choice. Markland states that its optical detector automatically adjusts beam intensity to accommodate thick or thin concentrations and can continue reading while solids in the probe gap remain higher than solids in scum layers on the windows. Require representative sludge samples, operating observations, and cleaning-access details before treating that fouling tolerance as sufficient for the site.
Build the Site-Input Sheet

Use one common input sheet for every bidder so responses remain technically comparable. Ask the plant operator for the process and sludge information, the equipment supplier for instrument range and installation requirements, and the controls contractor for confirmation of the control interface.
- Request a dimensioned tank drawing showing liquid depth, sludge-interface operating range, surface skimmers, scraper travel, obstructions, mounting points, and cable-routing access.
- Request representative sludge information covering solids concentration, settling behavior, expected rate and range of level change, entrained solids, grease, fibers, and fouling tendency.
- Confirm electrical supply, control-panel space, hazardous-area classification, required output signals, communications protocol, and integration responsibility.
- Record the intended function of the instrument: display, high and low alarms, underflow-pump sequencing, analog control, centralized monitoring, or a combination.
- Define the required consequence of high sludge level, low sludge level, signal loss, and recovery before suppliers select fail-safe outputs.
The drawing and sludge record must use the same datum. If the plant reports level from the liquid surface but the sensor measures depth from the tank bottom, require the supplier to state its reference point, top and bottom offsets, indicated resolution, and how the value will be presented to operators. Do not approve a proposal that merely says the sensor is “suitable for the tank.”
Specify Controls, Outputs and Failure Behavior
Write the control sequence into the purchase specification. Markland supports two independently adjustable high and low setpoints, a linear 4–20 mA output, and optional RS-485 communication. Its control description uses the low setpoint to operate the underflow pump and the high setpoint as an excessive-sludge-depth alarm. Confirm whether that logic matches the plant’s existing pump sequencing, run limits, and operator override.
Define how short process disturbances are filtered. Markland states that the actual sludge depth must exceed a setpoint continuously for 30 seconds before its relay energizes, while a 10-second continuous delay is required before de-energization. Treat these as supplier-specific controls; ask every bidder to state its switching delays, whether they apply separately to each relay, and how the behavior appears in the PLC.
Specify fault behavior before signature. Markland reports that a fault de-energizes both relays and sends the 4–20 mA output to zero. For each proposal, require a written statement of what happens on power loss, invalid level, out-of-range level, loss of communications, and sensor disconnection. Include whether the last reading is held, whether recovery is automatic, how the fault is annunciated, and whether the control contractor must implement a separate hard-wired interlock.
Define the integration route. Badger Meter states that EchoSmart sensors require no calibration and that field networks may connect measurement data to the control system through a digital-to-analog converter. Require the bidder to nominate the converter, define its signal conversion, provide the communications protocol, and identify who configures the PLC and tests end-to-end control operation.
Define Installation, Maintenance and Acceptance Tests

Make fouling control, safe isolation, and proof of performance explicit quote items. Badger Meter recommends frequent inspection during the first 3 to 6 months to establish a site-specific cleaning regimen and states that the measurement surface should remain clear. Markland states that its probe must eventually be removed and wiped with a soft cloth. The quotation should include removal access, safe isolation, cleaning tools, replacement parts, and a defined maintenance responsibility.
| Quote line item | Technical scope to specify | Red flags to check before signing |
|---|---|---|
| Measurement performance | Measurement datum, required span, displayed resolution, accuracy claim, interface indication, out-of-range indication, and signal-loss behavior. | A range that does not cover the expected operating zone or an accuracy statement with no test method. |
| Setpoints and relay logic | Independent high and low setpoints, energize and de-energize delays, pump-start and pump-stop assignments, alarm outputs, and local reset behavior. | Unspecified timing, undocumented relay states, or a logic sequence that conflicts with existing pump controls. |
| Signal and communications | Signal type, electrical details, network protocol, converter or gateway, PLC point list, signal continuity, and loss indication. | Protocols are named without connection details, or PLC integration and configuration are excluded. |
| Installation | Drawing approval, mounting components, cable route, obstruction clearance, scraper interaction, electrical connection, panel configuration, and commissioning. | Cabling, penetrations, controls integration, travel clearance, or site labor are omitted from the price. |
| Fouling and maintenance | Cleaning method, inspection plan, safe isolation, probe-removal access, cleaning tools, spare parts, and operator training. | No maintenance owner, no removal access, or fouling is described only as “self-cleaning.” |
| Acceptance and delivery | Factory and site tests, documentation, training, commissioning dates, spare parts, and a delivery schedule covering drawing approval through handover. | Acceptance relies only on a display check, with no signal-loss, communication, or interlock test. |
Require factory and site acceptance tests for indicated level, high and low setpoint operation, relay transitions, signal continuity, signal-loss indication, communications, and control interlocks. The test procedure should identify the reference method, test points, acceptance tolerance, and responsible party. Delivery should be scheduled as a chain: sensor selection, drawing approval, panel configuration, installation, commissioning, operator training, documentation, and spare-parts handover.
Integrate the Sensor with Sludge Handling Equipment
Connect blanket control to the selected sludge-handling route before approving the instrumentation. Markland describes automatic underflow-pump control from a low setpoint and an alarm from a high setpoint. Verify that this sequence will not withdraw excessive water, overdraw the blanket, or conflict with the plant’s minimum sludge-inventory rule. Specify whether pump operation is driven directly by the sensor relay, through the PLC, or subject to an existing timer and interlocks.
Where downstream dewatering is included, compare the sensor’s withdrawal function with the hydraulic and solids-handling duties of a plate-and-frame sludge dewatering system. The blanket sensor controls removal from the clarifier or DAF unit; it does not establish the feed consistency, polymer demand, or dewatering capacity of downstream equipment. Identify those as separate project responsibilities.
For DAF installations, confirm how the selected sensor coordinates with the dissolved air flotation system. Markland describes a detector application for the sludge/liquid interface in DAF thickeners, but the quotation must identify whether the measurement refers to float depth, clarified-liquid interface, or another process boundary. The sensor should support the DAF operating strategy rather than remain an isolated monitoring accessory.
Require each quotation to list excluded installation, cabling, control integration, sludge-handling modifications, and site services. An exclusion is useful only if it is assigned to a named party and included in the project schedule.
Further Reading
Frequently Asked Questions
How does the required blanket range change the sensor choice?
Define the expected minimum and maximum interface positions from a stated datum, then require every bidder to demonstrate that its proposed measurement span covers that operating zone. For comparison, the cited Markland optical configuration is adjustable from 0–700 cm or in. Do not select from nominal range alone: also obtain the mounting location, display resolution, accuracy method, and out-of-range behavior.
Do we need local controls, remote monitoring, or both?
Base the decision on the operating sequence. If pumps require local autonomous control, specify relays, setpoints, and delay behavior. If the plant needs central visibility, require the analog or network output, PLC point list, and loss-of-communications response. For a combined arrangement, identify which functions remain available locally when the plant network is unavailable.
How do fouling and maintenance affect the total cost of ownership?
Ask each supplier for its inspection interval, cleaning method, safe-isolation requirement, probe-removal access, spare-parts recommendation, and labor responsibility. Badger Meter recommends frequent inspection during the first 3 to 6 months to establish a site-specific cleaning regimen, while Markland states that its probe eventually must be removed and wiped with a soft cloth. The comparison should include the labor and access consequences of those statements.
Which documents and site tests should appear in the purchase order and quotation?
Require the signed quotation to identify the measurement datum and span, electrical and communications details, relay and fault behavior, mounting arrangement, cleaning